Electrical Engineering · Power Systems
The yearly load duration curve of a generating station is considered a straight line from a maximum load of 30 MW to a minimum load of 20 MW. If the capacity of the plant is 35 MW, what are the load factor, plant capacity factor, and utilization factor respectively?
- 10.833, 0.314 and 0.857
- 20.333, 0.714 and 0.857
- 30.833, 0.714 and 0.857✓
- 40.833, 0.714 and 0.557
Correct answer
0.833, 0.714 and 0.857