In a two-machine system connected through a transmission line of reactance X, the initial rotor angles of the generators are δ1 = 45° and δ2 = 30° (power flows from machine 1 to machine 2). After a disturbance, the rotor angles change to δ1' = 35° and δ2' = 20°, respectively. Assuming constant generator internal voltages and line reactance, what happens to the power exchanged between the two generators?
- 1The magnitude of power exchanged increases, but the direction remains unchanged.
- 2The magnitude of power remains identical, but the direction of power exchange is reversed.
- 3Both the magnitude and direction of the power exchange remain completely unchanged.
- 4The magnitude of power exchanged decreases, but the direction remains unchanged.✓
Correct answer
The magnitude of power exchanged decreases, but the direction remains unchanged.