Consider a 20 kVA, 2200/200 V, 50 Hz single-phase transformer. Test results are: OC Test: 220 V, 4.2 A, 150 W (LV side) SC Test: 88 V, 10 A, 366 W (HV side) Determine the voltage regulation at full load with 0.8 lagging power factor.
- 15.19%
- 22.25%
- 34.25%
- 43.19%✓
Correct answer
3.19%