Calculate the double line-to-ground (LLG) fault current in p.u. for a generator operating at 1.0 p.u. voltage, if the positive, negative, and zero sequence reactances up to the fault point are 0.08 p.u., 0.07 p.u., and 0.05 p.u. respectively. (Neglect resistances)
- 115.0 p.u.
- 211.5 p.u.
- 316.0 p.u.✓
- 412.5 p.u.
Correct answer
16.0 p.u.