According to standard electrical installation practice (such as IS 732), the permissible leakage current in an installation must not exceed 15000 of the full-load current. For a building installation with a 2.4 kW load on a 240 V system of supply, what will be the minimum permissible insulation resistance to earth?
- 10.24 MΩ
- 20.12 MΩ✓
- 30.05 MΩ
- 40.08 MΩ
Correct answer
0.12 MΩ