A three-phase load of 100 kW at 0.6 lagging power factor is connected to a 400 V line. Calculate the total kVAR of the star-connected capacitor bank required to improve the power factor to 0.9 lagging.
- 184.9 kVAR✓
- 248.4 kVAR
- 392.4 kVAR
- 4100.0 kVAR
Correct answer
84.9 kVAR