A power system has two synchronous generators. The governor-turbine characteristics corresponding to the generators are: P1 = 50(50 - f) and P2 = 100(51 - f) Where 'f' denotes the system frequency in Hz and P1 and P2 are respectively, the power outputs (in MW) of turbines 1 and 2. Assuming the generators and transmission network to be lossless, the system frequency for a total load of 400 MW is:
- 149.0 Hz
- 248.5 Hz
- 348.0 Hz✓
- 447.5 Hz
Correct answer
48.0 Hz