A load rated at 100 kVA operates at a power factor of 0.6 lagging. If the active power is kept constant and power factor correction improves it to 0.9 lagging, find the reduction in kVA demand.
- 120 kVA
- 230 kVA
- 333.3 kVA✓
- 440 kVA
Correct answer
33.3 kVA