A generating station supplies power through four feeders. The maximum demands for the four feeders are 16 MW, 10 MW, 12 MW, and 7 MW respectively. If the overall maximum demand on the generating station is 15 MW and the load factor is 60%, find (a) the value of diversity factor and (b) the number of units generated annually.
- 1a) 3.00 and b) 78,840 MWh✓
- 2a) 3.00 and b) 12,000 MWh
- 3a) 2.25 and b) 78,840 MWh
- 4a) 2.25 and b) 12,000 MWh
Correct answer
a) 3.00 and b) 78,840 MWh