A 3-phase, 11 kV, 6 MVA Y-connected alternator has a synchronous impedance of (1 + j10) Ω per phase. Its excitation produces a line-to-line generated EMF of 14 kV. When connected to an infinite bus-bar at 11 kV, determine the maximum power output possible.
- 116.66 MW
- 214.21 MW
- 315.41 MW✓
- 416.01 MW
Correct answer
15.41 MW