Electrical Engineering · Electrical Machines
A 11000 kVA, 3-phase, star-connected, 11000 V, two-pole turbo generator has the following data: Open circuit core loss at 11000 V = 50 kW Windage and Friction loss = 45 kW Short circuit load loss at 578 A = 100 kW Field Current = 50 A Field winding resistance = 2 Ω Ignoring the change in field current, calculate the efficiency at rated load and 0.8 power factor leading.
- 192.1%
- 297.8%✓
- 388.5%
- 485.6%
Correct answer
97.8%